The Victron VM-3P75CT energy meter is a standard device to measure the power and energy of single- and three-phase applications and calculates each phase's power values and broadcasts this over VE.Can or Ethernet with a high rate. It has built-in Ethernet and VE.Can ports for connecting to a GX device and the split-core current transformers enable easy and quick installation without modifying existing wiring.
The energy meter works out of the box (the firmware may need to be updated; details can be found in the Firmware Updates chapter) as a grid meter for systems with a MultiPlus and Quattro. Configuration (via VictronConnect) is only required for changing the role and manual IP configuration rather than the default DHCP. Its data is displayed on a GX device such as the Cerbo GX or Ekrano GX, as well as in VictronConnect and the VRM Portal.
Specifications:
Voltage connection: Direct
Input voltage range L-N: 85 to 265VAC
Input voltage range L-L;150 to 460VAC
Frequency: 50/60Hz
Current connection: Via current transformers (included - wire length 640mm (25.2in)
Rated current: 75A
VE.Can communication port: Two RJ45 connectors (VE.Can terminators included)
Ethernet communication port: One RJ45 connector, Modbus UDP
Refresh rate: 100ms
Type: Self-power supply via L1-N
Switch or circuit breaker: Required as means of a disconnecting device - not included
External fuse [1]: Required in the neutral conductor - 500mA, not included
Consumption: 1.45W / 3.1VA
Frequency: 50/60Hz
Material & Color: Polycarbonate, blue (RAL5012)
Voltage connection: Screw terminals 0.25 - 1.5mm2 (24 - 16AWG)
Current transformer connection: Pluggable screw terminals (included)
Protection category: IP20
Weight: 370g (including packaging)
Dimensions: 90 x 71 x 59mm (3.5 x 2.8 x 2.3in)
Indoor/outdoor usage: Indoor only
Operating temperature: From -10 to +55 °C
Storage temperature: From -20 to +70 °C
Relative humidity: < 90% non-condensing
Altitude: 2000m (6562ft)
Mains supply voltage fluctuations: ±0.1Vin
Overvoltage category: Cat. III
Pollution degree: 2